Strobe Connection
The strobe assembly provides visual indication of alarm conditions, and is connected to the indicator/control assembly via the provided polarized connector. To install the strobe module, simply plug the provided connector onto the pins as indicated on the rear of the indicator/control module. Snap the strobe lens into the cover plate, and install cover plate following completion of remote module wiring.
NOTE: The strobe and audible buzzer features are not ADA compliant, and not intended for life safety notification or evacuation purposes (public mode). These functions are for duct smoke detector status indication only (private mode).
Audible Buzzer Configuration
There are two jumpers located on the rear of the indicator/control assembly. To enable audible buzzer operation for Alarm or Trouble conditions, simply leave the jumpers in place. To disable either or both functions, remove the appropriate jumper(s).
Silence and Ringback Functions
On the occasion where an audible alarm or trouble condition needs to be silenced while the detector condition is inspected and remedied, the indicator/control module provides a silence function. The slide switch located on the front of the module is pushed DOWN to activate the silence function.
Upon correction of the notified condition, the silenced buzzer will resume sounding. The ringback feature serves as a reminder to reset the silence switch to the “normal”, UP position. Note that the strobe module, when installed, will not stop operating when the silence function is engaged.